Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2018, for assembly occupancy (A2)
06/01/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
2. Show that each heat pump meets the requirements of Section C403.5, IECC 2018 (economizers) unless exempted by compliance with the efficiency requirements of Table C403.5 (2) and Section C503.4.1, IECC 2018
06/01/2020 ROBERT SHERRY WATER REVIEW Completed
06/02/2020 ALEXANDRA HINES ZONING REVIEW Reqs Change The adjacent unit seems to be a less intensive land use. Either:
a. Show that CofO that adjacent unit was food service or
b. Apply for development package to show compliance on site plan with development standards, like 1:100 parking ratio. Once approved, zoning will cross-check building plan with site plan for consistency.
06/02/2020 AHINES2 ENGINEERING REVIEW Passed
06/02/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/02/2020 MARTIN BROWN FIRE REVIEW Approved
06/02/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Scope of Work: The Scope of Work indicates "Existing Restroom No Change". The occupant load has changed with the addition of the new adjacent space. This requires a new analysis using the International Existing Building Code. Please provide the plumbing fixture requirements for restrooms, lavatories, and service sinks. Indicate accessibility requirements per the IEBC.
2. Sheet A3; Floor Plan: Per the IBC Section 1109.11, 5% of all standing and seating spaces must be accessible. Please indicate this calculation on the drawing, and show those spaces on the Floor Plan.
3. General: Please provide written responses to all review comments.
06/02/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed