| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/02/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/16/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Approved | |
| 06/25/2020 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
| 06/30/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Identify the service name on the line diagrams. Which one is A, B, andC? 2. Provide a placard at each service location per 705.10. 3. What is the distance between the existing Eaton Load Center and the new 400 amp service disconnects. Also the location of the existing Eaton Load Center. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements |
| 07/09/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |