Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM03300
Parcel: 141185940

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM03300
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Include the floor drain and lavatory for the north restroom on the waste and vent diagram.
2. Include the gas piping in the plumbing plan. Show the existing gas meter in its actual location and provide the total developed pipe length to each gas connection.
3. Verify that the distance from the hot water source (e.g. a recirculating hot water loop) to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018 (i.e. 24" for ½" pipe, 6" for ¾" pipe).
07/08/2020 ROBERT SHERRY WATER REVIEW Reqs Change 1. Provide the size and serial number of the existing water meter. Reference: Section 107.2.1, IBC 2018.
2. The water pipe sizing calculations are based on an assumed water pressure of 60 PSI but the data from Tucson Water indicates the expected pressure range will be 35-42 PSI. The shell building included the installation of a booster pump for the sole use of Der Wienerschnitzel, located in the location currently showing the installation of the water heater.
07/14/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show that the walk-in cooler meets the construction requirements of Section C403.10.2, IECC 2018.
2. Show that the walk-in cooler meets the efficiency requirements of Section C403.10.2.1, IECC 2018
3. Update the ventilation calculations to coordinate with Table 403.3.1.1, IMC 2018 with respect to the kitchen and sales ventilation requirements.
4. Clarify the exhaust flow rate for KEF-3. The exhaust fan schedule on sheet M5.0 shows 900 CFM but the CaptiveAire hood information on sheet M2.0 calls for only 850 CFM. Reference: Section 107.2.1, IBC 2018.
5. Verify that the evaporative cooling section of the makeup air unit is equipped with a recirculating water system. Reference: Section 928.2, IMC 2018 and ARS Title 45, Chapter 1, Article 12. See text at: (http://www.azleg.gov/viewdocument/?docName=http://www.azleg.gov/ars/45/00313.htm).
07/16/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Ref; Plan Sheet E1. Where is the legend that describes what encircled notes 1 and 2 located on the one line diagram refer to?
2. The line diagram shows Panel A feeding Panel C, the panel schedules show Panel B feeding Panel C. Please clarify.
3. Revise the 2012 IECC to the current 2018 IECC.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.
07/22/2020 JPEELDA1 FIRE REVIEW Approved
07/24/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/24/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet T1.1; Occupancy (Plumbing); Occupancy (Exiting): The Plumbing Occupancy indicates 22 persons in the 1620 SF, while the Exiting Occupancy indicates 39 persons in the 1620 SF. Please clarify.
2. Sheet T1.1; Exiting Plan: The north exit indicates 3 occupants and the south exit indicates 34 occupants for a total of 37 occupants. The Exiting Occupancy is indicated as 39. Please coordinate.
3. Sheet T1.1; Building Codes: Please add the 2009 ICC/ANSI A117.1 Accessibility Code.
4. Sheet T1.1; Tactile Exit Signage: The first note references 5/A9.2 for signage design and mounting requirements. Please revise that reference.
5. Sheet T1.1; Tactile Exit Signage: The second note references 9/A9.2 for accessible signage mounting/clearance requirements. Please revise that reference.
6. Sheet T1.1; Tactile Exit Signage: The third note references 10/A9.2 for tactile egress signage mounting requirements. Please revise that reference.
7. Sheet A1.0; Site Keynotes: Note SP-12 was not located on the plan. Please verify.
8. Sheet A2.1; Wall Legend: The first note references 4/A8.4 for typical wall types. Please revise that reference.
9. Sheet A2.1; Symbols: The first symbol references Sheet A7.4 for window type information. Please revise that reference.
10. Sheet A2.1; Symbols: The second symbol references Sheet A7.3 for door information. Please revise that reference.
11. Sheet A2.1; Symbols: The fourth symbol references Sheets A14.1 and A14.2 for turning radius information. Please revise that reference.
12. Sheet A2.1; Floor Plan Keynotes: Note FP-07 references 1/A9.2 for disabled access signage. Please revise that reference.
13. Sheet A2.1; Floor Plan Keynotes: Please complete Note FP-08.
14. Sheet A2.1; Floor Plan Keynotes: Note FP-11 references 5/A9.2 for tactile exit signs. Please revise that reference.
15. Sheet A6.1; Restroom Elevations 105A and 106C: Please indicate the vertical grab bar per the ICC/ANSI Figure 604.5.1.
16. Sheet A9.1; Detail 3: Please indicate the vertical grab bar per the ICC/ANSI Figure 604.5.1, including dimensions.
17. General: The professional seal of the registered architect must include the date the seal was signed. Please provide (all applicable sheets).
18. General: The professional seal of the registered civil engineer indicates the expiration date rather than the date the seal was signed. Please provide (all applicable sheets).
19. General: Please provide written responses to all review comments.
08/05/2020 LOREN MAKUS ENGINEERING REVIEW Approved
08/14/2020 NICHOLAS ROSS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/20/2020 JGARCIA1 APPROVAL SHELF Completed
08/20/2020 JGARCIA1 OUT TO CUSTOMER Completed
08/20/2020 JGARCIA1 REJECT SHELF Completed