Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide detailed information for the line tap. Verify by the manufacturer of the equipment that this tap onto existing bus will not compromise the performance or listing of the equipment. NEC 110.3. 230.66
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.