Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM03255
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/28/2020 | MALLORY RESS | ZONING | REVIEW | Approved | |
| 05/28/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 05/29/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide hot water to the sink in the utility room. Reference: Section 607.1, IPC 2018. 2. Provide temperature and pressure reief discharge piping to an approved location. Reference: Section504.6, IPC 2018. 3. Provide thermal expansion control for storage-type water heaters. Reference: Section 607.3, IPC 2018. |
| 05/29/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 05/29/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/01/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 06/01/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 06/01/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/01/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |