| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/24/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed. [Second comment: The submitted ventilation calculation uses 3 occupancies: nail salon, entry lobby, and office. It also does not include the ventilation required for the floor area (0.12 CFM/Square Foot). Since you have only one air handler, you need to ventilate the suite as if it is one occupancy - a nail salon.] [Initial comment: Complete the ventilation calculations. Air from the nail salon may not be recirculated to other occupancies. Reference: Section 403.2.1 (3), IMC 2018.] 2. Comment not addressed. [Second comment: With 17 nail stations, 850 CFM of local exhaust is required.] [Initial comment: Provide 50 CFM of exhaust per nail station. Reference: Footnote h, Table 403.1.1, IMC 2018.] 3. Comment not addressed. [Initial comment: The clouded note on the mechanical plan calls for a new exhaust fan to move 700 CFM while the same fan is shown on the duct diagram (B3/M0.1) as moving 400 CFM.] 4. Comment not addressed. [Initial comment: Provide adequate make-up air to the suite so that the suite pressure remains essentially neutral. Don't forget to include the continuous restroom exhaust when determining the outside air requirements. Reference: Section 501.4, IMC 2018.] |
| 07/24/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed. [Second comment: Provide tempered water for the lavatory in the public restroom using a thermostatic mixing valve listed to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.] [Initial comment: Verify that the installation of the thermostatic mixing valve conforms to the manufacturer's installation instructions.] 2. Comment not addressed. [Initial comment: Provide a metering faucet for the restroom lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.] |
| 08/05/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | No compliance with the previous plan review comments. 2 seperately circuited exhaust fans identified as Exh F#1. 2017 NEC 408.4 |