Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM03234
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/22/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. As requested per the precious electrical plan review. The lighting plan clearly shows 2 exhaust fans at different locations with their own designated branch circuit. Both fans are labeled #1. Please clarify. Also show the sequence of operation that correlates with the mechanical plans. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 07/22/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The submitted ventilation calculation uses 3 occupancies: nail salon, entry lobby, and office. It also does not include the ventilation required for the floor area (0.12 CFM/Square Foot). Since you have only one air handler, you need to ventilate the suite as if it is one occupancy - a nail salon. [Initial comment: Complete the ventilation calculations. Air from the nail salon may not be recirculated to other occupancies. Reference: Section 403.2.1 (3), IMC 2018.] 2. With 17 nail stations, 850 CFM of local exhaust is required. [Initial comment: Provide 50 CFM of exhaust per nail station. Reference: Footnote h, Table 403.1.1, IMC 2018.] 3. The clouded note on the mechanical plan calls for a new exhaust fan to move 700 CFM while the same fan is shown on the duct diagram (B3/M0.1) as moving 400 CFM. 4. Provide adequate make-up air to the suite so that the suite pressure remains essentially neutral. Don't forget to include the continuous restroom exhaust when determining the outside air requirements. Reference: Section 501.4, IMC 2018. |
| 07/22/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide tempered water for the lavatory in the public restroom using a thermostatic mixing valve listed to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018. [Initial comment: Verify that the installation of the thermostatic mixing valve conforms to the manufacturer's installation instructions.] 2. Provide a metering faucet for the restroom lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. |