| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/28/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/29/2020 | ALEXANDRA HINES | ZONING | REVIEW | Approved | |
| 05/29/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Complete the ventilation calculations. Air from the nail salon may not be recirculated to other occupancies. Reference: Section 403.2.1 (3), IMC 2018. 2. Provide 50 CFM of exhaust per nail station. Reference: Footnote h, Table 403.1.1, IMC 2018. |
| 05/29/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide full compliance with the 2018 IECC for the lighting. Both exhaust fans are identified as EF-1. Please clarify. 2018 IBC 107.2.1, 2017 NEC |
| 05/29/2020 | AHINES2 | ENGINEERING | REVIEW | Passed | |
| 05/29/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/29/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/29/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide the listing information for the pedicure chairs. 2. Verify that the installation of the thermostatic mixing valve conforms to the manufacturer's installation instructions. |
| 05/29/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |