Permit Number: T20CM03220
Parcel: 126070900

Address:
4025 E KILMER ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T20CM03220
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T20CM03220
PLAN REVIEW COMMENTS


Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. A dwelling unit providing complete independent living facilities requires compliance with design ordinances for handicap, solar water, photo-voltaic and gray water preparations. Design Ordinances adopted by the City of Tucson.
2. Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc.
3. All SFR and Duplex plans submitted after July 1, 2009 require a solar photo-voltaic
4. Each dwelling unit building requires a street address and a separate permit, R319.
5. A new dwelling unit requires collection of development impact fee when the building permit is processed, City of Tucson Ordinance #11203.

SITE PLAN:

1. Show compliance with the Pool Barrier requirement by including a pool alarm system for doors and windows open to the pool, or show a continuous barrier around the pool, 2018 ISPSC.

FLOOR PLANS:

1. Show a maximum ½” floor elevation change at a notated accessible route entrance on the floor plan, R106.1.1.

STRUCTURAL PLANS:

1. Show a beam size with appropriate load carrying capacity, R301.1. The 6x8 porch beam is undersized for the 16’ span.

SECTIONS - DETAILS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation, or controlled exhaust with a calculated airflow rate, R303.4; N1103.6 & M1505.4. Show the system and appropriate flow rate setting on the plans. A one bedroom dwelling under 1500 SF requires a 40 CFM continuous setting.

ELECTRICAL PLANS:

1. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3.
2. Clothes Washer and Dishwasher GFCI: receptacles require readily accessible protection typically from an upstream device, E3902.9 & 10. Add notation to plans.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
09/11/2020 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Submit a copy of the signed floodplain use permit application with the resubmittal.
2. The base flood elevation for this new structure is 2512.1 NAVD88. The regulatory flood elevation is 2513.1. Show the RFE as the floor elevation for the new structure.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/14/2020 SROGERS2 OUT TO CUSTOMER Completed