Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T20CM03182
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/26/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/26/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/26/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 05/26/2020 | SAMUEL ROGERS | ZONING | REVIEW | Approved | |
| 05/27/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A-1; Detail 3: Please provide a U.L. Listing Number, or an Item Number from the IBC Table 721.1(2) for the wall and ceiling assemblies. 2. Sheet A-1; Basement Floor Plan 1: Please indicate in the Basement Floor Plan Keyed Notes #2 the fire resistance rating of the double door. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/03/2020 | ARUIZ1 | OUT TO CUSTOMER | Completed |