Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM03177
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/26/2020 | ALEXANDRA HINES | ZONING | REVIEW | Reqs Change | 1) Approval of DP20-0107 is required prior to approval of the building plans |
| 05/26/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | 1) Approval of DP20-0107 is required prior to approval of the building plans |
| 05/26/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Why is only the 400 amp service metered? See one line diagram. 2. The new Feeders to the new disconnects are extensions of the service conductors to the new meters for the MRI Project. Grounding conductors ahead of the service disconnects to be sized per NEC 250.66. 3. Provide a grounding detail for the modified service arrangement and the 112KVA transformer.. 4. How is the new MRI Mobile Trailer powered. 5. The load calculations show the MRI load at 312 amps. Is this fed from the 200 amp disconnect? Please clarify. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements |
| 05/26/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/26/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A-0; Code Review: Please indicate the square footage of the new mobile trailer. The SF and occupant load for this mobile trailer must be added to the total building SF and the total building occupant load, and indicated on the permit drawings. |
| 05/27/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 05/27/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 05/27/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/29/2020 | ARUIZ1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |