Permit Number: T20CM03153
Parcel: 13405119Q

Address:
9491 E 22ND ST

Review Status: Active

Review Details: OTHER

Permit Number - T20CM03153
Review Name: OTHER
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide an economizer for the proposed packaged heat pump unit along with a means for relieving the excess air during economizer operation or increase the efficiency of the rooftop unit per Table C403.5 (2), IECC 2018 (i.e. minimum 15.4 SEER). Reference: Section C403.5, IECC 2018.