Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T20CM03138
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/20/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 07/20/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 07/20/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 07/20/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 07/22/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Per the last electrical plan review comment. It was requested to provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. Per the response the plan change only reflected the new 'C' type luminaires… What about the 'EX' luminaires also appear to be exterior, under a canopy? Please clarify. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/05/2020 | JGARCIA1 | APPROVAL SHELF | Completed |
| 08/05/2020 | JGARCIA1 | OUT TO CUSTOMER | Completed |
| 08/05/2020 | JGARCIA1 | REJECT SHELF | Completed |