Permit Number: T20CM03123
Parcel: 11504445C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM03123
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2020 MARTIN BROWN FIRE REVIEW Approved
05/22/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a metering faucet for the lavatory in room 114, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. At a minimum, coffee machines and non-carbonated beverage dispensers require the use of a backflow preventer listed to either ASSE 1022, ASSE 1024, or an air gap. Reference: Section 608.17.1.2, IPC 2018.
05/22/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/22/2020 ROBERT SHERRY WATER REVIEW Completed
06/02/2020 LOREN MAKUS ENGINEERING REVIEW Passed
06/08/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: Vantage West Credit Union - 801 E Speedway
T20CM03123
Building Facade Remodel Plan (1st Review)

TRANSMITTAL DATE: June 8, 2020

1. Zoning has reviewed the building plans for compliance with development package DP20-0071. Until DP20-0071 has been approved Zoning cannot approve the building plans.

2. Zoning cannot approve the building plans until PDSD Commercial Plans reviewers have approved the building plans.

3. The development package sheets provided in the building set either need to be the approved development package sheets, marked as for reference only, or removed from the plan set.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
06/16/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting. Include the 'E' luminaires in the luminaire schedule and exterior lumen calcs.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code
06/23/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
06/23/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/24/2020 VLEON1 APPROVAL SHELF Completed
08/24/2020 VLEON1 OUT TO CUSTOMER Completed
08/24/2020 VLEON1 REJECT SHELF Completed