Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM03087
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/20/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/21/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Verify that the specified sensor faucet for the public lavatories has an automatic time-out so that it will dispense a maximum of 0.25 gallons per metering cycle. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1. 2. Verify that the pipe sizes called out for the flush valves (e.g. water closets and clinical sinks) will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper, PEX, or CPVC piping). At a minimum design flow rate of 25 GPM for a siphonic, flush-valve water closet, a 1" Type L copper pipe has a flow velocity of 9.7 FPS. Reference: Table 604.3, IPC 2018. 3. Provide a design for the proposed changes to the medical gas system. Reference: Section 107.2.1, IBC 2018. |
| 05/21/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/22/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 06/02/2020 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
| 06/03/2020 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 06/16/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. The panel schedules all the panels as existing except panel 'EC2'. Provide a complete One Line Diagram, include load calcs. 2. Provide tamper resistant receptacles as required per NEC 406.12.5. 3. Provide complete compliance with the 2018 IECC for the lighting. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
| 07/01/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.51; Noted Floor Plan: Please reference on this sheet that casework elevations are indicated on Sheet A8.01. 2. Sheet A1.51; Notes: Please specify in Note 8 the upgrades required to the existing walls. 3. Sheet A1.51; Noted Floor Plan: An enlarged plan at the Patient Toilet references A/A2.01. Please revise that reference. 4. Sheet A2.00; Toilet Accessories Legend: The vertical grab bar (W) indicates 33"/40" to the centerline. The ICC/ANSI Figure 604.5.1 indicates 39" to 41". Please verify. 5. Sheet A2.00; Toilet Accessories Legend: Where are the grab bars C and D located? Please verify. 6. Sheet A8.01; Casework Elevation 1 in Meds 143: A detail references 3/A8.51 at the wall cabinet. Please revise that reference. 7. General: Please provide north arrows on all plans. 8. General: Please provide written responses to all review comments. |
| 07/01/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/21/2020 | JGARCIA1 | APPROVAL SHELF | Passed |
| 07/21/2020 | JGARCIA1 | OUT TO CUSTOMER | Completed |
| 07/21/2020 | JGARCIA1 | REJECT SHELF | Completed |