Permit Number: T20CM03076
Parcel: 12510025E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM03076
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2020 ELISA HAMBLIN ZONING REVIEW Approved
05/19/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Demonstrate energy code compliance for the alterations to the building envelope using calculations based on the current code. Reference: Sections C503.1 and C503.3, International Energy Conservation Code 2018.
05/19/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide complete compliance with the 2018 IECC for the lighting.
The current adopted NEC is 2017 not 2020.
05/19/2020 EHAMBLI1 ENGINEERING REVIEW Passed
05/19/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Show how the new waste and vent piping for the new restroom relates to the existing waste and vent piping. Reference: Sections 704.3 and 911.1, IPC 2018.
2. The second-floor deck does not have a means of secondary drainage. Provide structural calculations to show that the deck can safely support the maximum possible water depth caused by ponding if the primary drains are assumed to be blocked. Reference: Section 1101.7, IPC 2018.
3. Provide the dimensions of the deck scuppers. Reference: Sections 1106.5 and 1108.3, IPC 2018.
05/19/2020 ROBERT SHERRY WATER REVIEW Completed
05/19/2020 MARTIN BROWN FIRE REVIEW Approved
05/20/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A2.0; Wall Types: At the south wall of the Conference Room 206, a Wall Type F is indicated, but the plan appears to be a glass wall. Please verify.
2. Sheet S1.1; Foundation Keynotes: Note 2 was not located on the plan. Please verify.
3. General: Please provide a Special Inspection Certificate with Parts A and B completed. This form may be found at www.tucsonaz.gov/PDSD.
4. General: Please provide written responses to all review comments.
05/20/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed