Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM03076
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/19/2020 | ELISA HAMBLIN | ZONING | REVIEW | Approved | |
05/19/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Demonstrate energy code compliance for the alterations to the building envelope using calculations based on the current code. Reference: Sections C503.1 and C503.3, International Energy Conservation Code 2018. |
05/19/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide complete compliance with the 2018 IECC for the lighting. The current adopted NEC is 2017 not 2020. |
05/19/2020 | EHAMBLI1 | ENGINEERING | REVIEW | Passed | |
05/19/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Show how the new waste and vent piping for the new restroom relates to the existing waste and vent piping. Reference: Sections 704.3 and 911.1, IPC 2018. 2. The second-floor deck does not have a means of secondary drainage. Provide structural calculations to show that the deck can safely support the maximum possible water depth caused by ponding if the primary drains are assumed to be blocked. Reference: Section 1101.7, IPC 2018. 3. Provide the dimensions of the deck scuppers. Reference: Sections 1106.5 and 1108.3, IPC 2018. |
05/19/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
05/19/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
05/20/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A2.0; Wall Types: At the south wall of the Conference Room 206, a Wall Type F is indicated, but the plan appears to be a glass wall. Please verify. 2. Sheet S1.1; Foundation Keynotes: Note 2 was not located on the plan. Please verify. 3. General: Please provide a Special Inspection Certificate with Parts A and B completed. This form may be found at www.tucsonaz.gov/PDSD. 4. General: Please provide written responses to all review comments. |
05/20/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |