Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T20CM03075
Parcel: 11451137D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM03075
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2020 ELISA HAMBLIN ZONING REVIEW Approved
05/19/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The current occupancy type is business; a mercantile occupancy will require additional ventilation. Provide calculations to show that adequate ventilation is being provided.
05/19/2020 ERIC NEWCOMB ELECTRICAL-COMMERCIAL REVIEW Passed
05/19/2020 EHAMBLI1 ENGINEERING REVIEW Passed
05/19/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet TS.1; Floor Plan: The exit from the storage room is not allowed per the IBC Section 1016.2(5). Please remove the "Exit" designation at that door.
2. Sheet TS.1; Code Check: Please indicate on this sheet that only one exit is required per the IBC Table 1006.2.1.
3. Sheet TS.1; Floor Plan: The restroom access may not pass through a storage room (or two storage rooms) per the IBC Section 1104.5. Please revise the plan.
4. Sheet TS.1; Floor Plan: Please provide an enlarged plan of the restroom, indicating dimensions for clearance per the ICC/ANSI Figure 604.3.
5. Sheet TS.1; Floor Plan: Please provide dimensioned elevations for the restroom grab bars per the ICC/ANSI Figures 604.5.1 and 604.5.2.
6. Sheet TS.1; Code Check: Please revise the occupancy load calculation. Storage = 325/300 = 1.1; Retail = 860/60 = 14.4. The total occupant load is 15.5, or 16. This number will require a drinking fountain and a service sink per the IBC Table 2902.1.
7. Sheet TS.1; Code Check: For the occupancy classification, this is a change of use from a B to an M. Please revise.
8. General: Please provide written responses to all review comments.
7.
05/19/2020 ROBERT SHERRY WATER REVIEW Completed
05/19/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the plumbing fixture calculations per Section 403.1.1, IPC 2018 (i.e. the actual occupant load is 15.4, rounded up to 16 people).
2. Revise the access to the restroom so the route is not through a storage room. Refernce: Section 403.3.1, IPC 2018.
05/19/2020 MARTIN BROWN FIRE REVIEW Reqs Change Please provide a Hazardous Inventory Materials Statement, including ICC designations of explosives, and quantities.
05/19/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed