Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM03066
Parcel: 14043011A

Address:
7211 S PARK AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM03066
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/24/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/24/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Comment not resolved, the DCW branch lines to the flush-valve water closets are still shown as 1" on sheet 2-PL103. [Initial comment: Verify that the pipe sizes called out for the flush valves will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper piping). At a minimum design flow rate of 25 GPM for a siphonic, flush-valve water closet, a 1" Type L copper pipe has a flow velocity of 9.7 FPS. Reference: Table 604.3, IPC 2018.]
10/08/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/09/2020 STEVE SHIELDS ZONING REVIEW Approved
10/28/2020 STANTEC ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL COMMENTS

Sheets 2-EL101 and 2-EL102

1. The circuit for the elevator pit shall have only the light in the pit on that circuit per 2017 NEC Art. 620.24.

2. Provide the location of the elevator machine room/machine space and provide a lighting circuit as required by 2017 NEC Art. 620.23.


Page 2 of 2



Sheets 2-EP601 and 2-EP602

1. Clearly identify all circuits that supply power to exit/egress lighting unit equipment at the distribution board as required by 2017 NEC Art. 700.12(F).

2. Clearly identify existing loads being moved to the new panel and provide all the information required to verify code compliance.

Sheet 2-EP701

1. Provide the primary disconnect requirements for the transformers as required by 2017 NEC Art. 450.14.

2. Verify the ratings of Panels LP411, LP412, LP413, LP421, and LP422 to verify compliance with 2017 NEC Art. 110.9 and 110.10.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Electrical Reviewed By:
Russell Cox
Electrical Plans Examiner 480-687-6049
russell.cox@stantec.com