Permit Number: T20CM03065
Parcel: 14043011A

Address:
7211 S PARK AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM03065
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/18/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/18/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
05/18/2020 ROBERT SHERRY WATER REVIEW Completed
05/21/2020 MARTIN BROWN FIRE REVIEW Approved
06/02/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: Pima Community College - Aviation Technology Center Expansion
Foundation & Under Slab Utility Package
T20CM03065

TRANSMITTAL DATE: June 3, 2020

1. Zoning has reviewed the building plans for compliance with submitted development package DP20-0103. While the building plans are consistent with the submitted DP as it relates to the zoning review purview of the building footprint, building height, square footage, site conditions etc., zoning cannot approve the building plans until the DP has been approved and all PDSD Commercial Plans reviewers have approved the building plans.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
06/02/2020 LOREN MAKUS ENGINEERING REVIEW Passed
06/10/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide for UFER and GEC installation to ground the new electrical service(s). NEC 250
2. Verify that all conduits installed under slab and or footings that must be installed at the time of the foundation work are accounted for as applicable.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.
06/10/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
06/10/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved