Permit Number: T20CM03064
Parcel: 110035910

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T20CM03064
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Revise the dimensions of the four new scuppers. The minimum width for these scuppers is 9.42" based on the roof drainage calculations from the approved drawings. Reference: Section 1106.5, IPC 2018.]
2. Comment not addressed. [Initial comment: Provide secondary (overflow) roof drainage for the four new scuppers. The "overflow" openings in the collector boxes do not provide overflow protection for the roof. Reference: Sections 1101.7, 1108.1, 1108.2 and 1108.3, IPC 2018.]

Final Status

Task End Date Reviewer's Name Type of Review Description
11/05/2020 ARUIZ1 OUT TO CUSTOMER Completed