Permit Number: T20CM03064
Parcel: 110035910

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T20CM03064
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/14/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the dimensions of the four new scuppers. The minimum width for these scuppers is 9.42" based on the roof drainage calculations from the approved drawings. Reference: Section 1106.5, IPC 2018.
2. Provide secondary (overflow) roof drainage for the four new scuppers. The "overflow" openings in the collector boxes do not provide overflow protection for the roof. Reference: Sections 1101.7, 1108.1, 1108.2 and 1108.3, IPC 2018.
10/20/2020 STANTEC BUILDING-COMMERCIAL REVIEW Completed
10/20/2020 STANTEC ELECTRICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/20/2020 ARUIZ1 OUT TO CUSTOMER Completed