Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/14/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
10/14/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the dimensions of the four new scuppers. The minimum width for these scuppers is 9.42" based on the roof drainage calculations from the approved drawings. Reference: Section 1106.5, IPC 2018. 2. Provide secondary (overflow) roof drainage for the four new scuppers. The "overflow" openings in the collector boxes do not provide overflow protection for the roof. Reference: Sections 1101.7, 1108.1, 1108.2 and 1108.3, IPC 2018. |
10/20/2020 | STANTEC | BUILDING-COMMERCIAL | REVIEW | Completed | |
10/20/2020 | STANTEC | ELECTRICAL-COMMERCIAL | REVIEW | Completed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/20/2020 | ARUIZ1 | OUT TO CUSTOMER | Completed |