06/18/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a luminaire schedule and 2012 Tucson/Pima County Outdoor Lighting Code compliance for the exterior lighting.
2. Provide total building load calcs for the electrical service.
3. Verify GFI protection for the service per NEC 240.13 and 230.95.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.