Permit Number: T20CM03019
Parcel: 11105040C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM03019
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2020 LMAKUS1 ZONING REVIEW Approved
05/15/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/15/2020 LOREN MAKUS ENGINEERING REVIEW Passed
05/15/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Designing the site Electrical constitutes the practice of engineering. Provide plans sealed by an Arizona Registrant. Reference Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide a floor plan showing the locations of the 30KVA transformer and new panel.
3. Provide an electrical plan that shows the equipment that is connected to the new panel unless this information is shown on the buildout plans.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
05/15/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/15/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/15/2020 ROBERT SHERRY WATER REVIEW Completed
05/15/2020 JPEELDA1 FIRE REVIEW Approved
05/19/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved