Permit Number: T20CM03013
Parcel: 13613001T

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM03013
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/16/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Section C404.5.1, IECC 2018 requires the maximum pipe length from the hot water source to the hot water termination for the public lavatories to be no longer than 6" for ¾" pipe or 24" for ½" pipe (see Table C404.5.1, IECC 2018). [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.]
07/20/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Could not locate a written response to the electrical plan review comments as requested.
2. No compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.
08/03/2020 STEVE SHIELDS ZONING REVIEW Approv-Cond
08/11/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment; Sheet G1.1 (Building Code); Sheet ASP1 (Site Plan): The Building Code on Sheet G1.1 indicates a building SF of 8211, while the Site Plan indicates 8185. Please coordinate.
2. Previous Comment; Sheet D1.1; Keyed Notes: Note D1 indicates "Not Used". It is indicated on the Demolition Plan. Please clarify.
3. Previous Comment; General: Please provide a valuation (labor + materials) for this project. The Building review may not be approved without this value.
4. Previous Comment; General: Please provide a Special Inspection Certificate with Parts A and B completed. This form may be found at www.tucsonaz.gov/PDSD.
5. Previous Comment; General: Please provide written responses to all review comments

Final Status

Task End Date Reviewer's Name Type of Review Description
09/07/2020 PC_TGUTHEI1 REJECT SHELF Passed
09/07/2020 PC_TGUTHEI1 APPROVAL SHELF Passed
09/07/2020 PC_TGUTHEI1 OUT TO CUSTOMER Completed