Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM03013
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/16/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
07/16/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Section C404.5.1, IECC 2018 requires the maximum pipe length from the hot water source to the hot water termination for the public lavatories to be no longer than 6" for ¾" pipe or 24" for ½" pipe (see Table C404.5.1, IECC 2018). [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.] |
07/20/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Could not locate a written response to the electrical plan review comments as requested. 2. No compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
08/03/2020 | STEVE SHIELDS | ZONING | REVIEW | Approv-Cond | |
08/11/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment; Sheet G1.1 (Building Code); Sheet ASP1 (Site Plan): The Building Code on Sheet G1.1 indicates a building SF of 8211, while the Site Plan indicates 8185. Please coordinate. 2. Previous Comment; Sheet D1.1; Keyed Notes: Note D1 indicates "Not Used". It is indicated on the Demolition Plan. Please clarify. 3. Previous Comment; General: Please provide a valuation (labor + materials) for this project. The Building review may not be approved without this value. 4. Previous Comment; General: Please provide a Special Inspection Certificate with Parts A and B completed. This form may be found at www.tucsonaz.gov/PDSD. 5. Previous Comment; General: Please provide written responses to all review comments |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/07/2020 | PC_TGUTHEI1 | REJECT SHELF | Passed |
09/07/2020 | PC_TGUTHEI1 | APPROVAL SHELF | Passed |
09/07/2020 | PC_TGUTHEI1 | OUT TO CUSTOMER | Completed |