Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM03013
Parcel: 13613001T

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM03013
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The discharge pipe for a water heater pressure relief valve shall terminate no higher than 6" above grade. Reference: Section 504.6 (10), IPC 2018.
2. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
05/15/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Demonstrate energy code compliance for the alterations to the building envelope using calculations based on the current code (e.g. COMcheck Envelope Compliance). Reference: Sections C103.2, C303, C503.1, and C503.3, International Energy Conservation Code 2018.
2. Revise details 1/M2 and 2/M2. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. Neither roof drain terminates where surface runoff will not occur. Reference: Section 307.2.1, IMC 2018, as amended by the City of Tucson.
3. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018.
05/15/2020 ROBERT SHERRY WATER REVIEW Completed
05/20/2020 MARTIN BROWN FIRE REVIEW Approved
05/28/2020 LOREN MAKUS ENGINEERING REVIEW Passed
05/29/2020 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: O'Reilly Automotive - Tenant Improvement
T20CM03013
Building Plans (1st Review)

TRANSMITTAL DATE: May 29, 2020

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning cannot approve the building plans until approved by all other PDSD review agencies.

3. On the next submittal ensure that the drawings are submitted as a single pdf file.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
06/09/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for all modified or new exterior lighting.
2. Coordinate the sequence of operation with mechanical requirements for the bathroom exhaust fans. See Mechanical Plan Review Comments.
3. Indicate whether the electrical service and associated downstream equipment is new or existing.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.
06/29/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G1.1 (Building Code); Sheet ASP1 (Site Plan): The Building Code on Sheet G1.1 indicates a building SF of 8211, while the Site Plan indicates 8185. Please coordinate.
2. Sheet D1.1; Keyed Notes: Note D1 indicates "Not Used". It is indicated on the Demolition Plan. Please clarify.
3. General: Please provide a valuation (labor + materials) for this project. The Building review may not be approved without this value.
4. General: Please provide a Special Inspection Certificate with Parts A and B completed. This form may be found at www.tucsonaz.gov/PDSD.
5. General: Please provide written responses to all review comments.
06/29/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed