Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM02996
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/17/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. No written response from the designer was located, as requested. 2. The current adopted IECC is the 2018 not 2012. 3. The request for the 2012 Tucson/Pima County Outdoor Lighting Code compliance was not addressed. See section 104 for plan submittal requirements. The IECC is not to be confused with the Tucson/Pima County Outdoor Lighting Code. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 06/18/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |