Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM02923
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/11/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 05/11/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide structural calculations and details to show how the water-source heat pump units in excess of 200-pounds are to be connected to the building structure. Reference: Section 302.1, IMC 2018. 2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified water-source heat pump units. Reference: Section C403.1.1 and C403.3.1, IECC 2018. |
| 05/11/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/11/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/12/2020 | ALEXANDRA HINES | ZONING | REVIEW | Approved | |
| 05/12/2020 | AHINES2 | ENGINEERING | REVIEW | Passed | |
| 05/12/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet g2.0; Second Floor Plan: It appears from the plan a single exit (rated stairwell) is being provided for this space. Per the IBC Table 1006.2.1, a sprinklered B occupancy with a maximum occupant load of 49 allows a maximum common path of egress travel distance of 100 feet. The distance indicated on the plan is greater than the allowable for a single exit. Please verify. 2. Sheet g2.0; Second Floor Plan: In the corridor south of Office 218, Office 219, and the stair, an interior wall is indicated at the west end. In order not to consider this a dead end corridor, occupants would be required to exit through the Reception 203 area. This would require exit lighting per the IBC Section 1013. Please verify and place information on the drawing. 3. Sheet a2.0; Second Floor Reflected Ceiling Plan: Please indicate exit lighting on this plan, or add a reference note indicating the location of that lighting. 4. General: Please provide written responses to all review comments. |
| 05/12/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/13/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide complete compliance with the 2018 IECC for the lighting. |