Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM02920
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/07/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. The second plan submittal shows no change or response to the plan reviewers comment. The panel still appears to be in the bathroom.. The contractor told the plan reviewer that the panel was in the pantry and clearance required per NEC 110.26 would be addressed, however the (filed) 2nd plan floorplan still shows the panel partially behind the partition for the pantry wall supporting the door. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/07/2020 | VLEON1 | APPROVAL SHELF | Completed |
| 08/07/2020 | VLEON1 | OUT TO CUSTOMER | Completed |
| 08/07/2020 | VLEON1 | REJECT SHELF | Completed |