Permit Number: T20CM02920
Parcel: 10605085A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM02920
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2020 MARTIN BROWN FIRE REVIEW Passed
05/19/2020 JOHN VAN WINKLE ENGINEERING REVIEW Passed
05/29/2020 STEVE SHIELDS ZONING REVIEW Passed
06/05/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. It appears the electrical panel is located in the bathroom or pantry. This is in violation of NEC art 240.24E or 110.26.
Insure that there is adequate working clearance about the panel as required per NEC 110.26. It is doubtful that can be achieved in the pantry.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
06/26/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/06/2020 AHINES2 OUT TO CUSTOMER Completed