Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM02876
Parcel: 11707270A

Address:
555 E 18TH ST

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T20CM02876
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/18/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the configuration of the natural gas sediment traps, as shown in detail 205/P5 , to comply with the requirements of Section 408.4, IFGC 2018 (i.e. the sediment trap is to be located downstream of the appliance shutoff valve, as close to the appliance as possible). [Initial comment: Provide sediment traps for the gas supply to the water heaters. Reference: Section 408.4, IFGC 2018.]
05/18/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/18/2020 MARTIN BROWN FIRE REVIEW Approved
05/20/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved