Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T20CM02876
Parcel: 11707270A

Address:
555 E 18TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02876
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2020 SAMUEL ROGERS ZONING REVIEW Approved
05/07/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The two Type I exhaust hoods require 1282 CFM of make-up air in addition to the make up air provided by EC-1. Provide a listing of the outside air that is currently being provided to the space that will provide the 1282 CFM of make up air. Reference: Section 508.1, IMC 2018.
05/07/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/07/2020 JOHN VAN WINKLE ENGINEERING REVIEW Passed
05/07/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Code Review: This building is considered an A-3 Occupancy Classification (arena) with an accessory use of restaurant/bar (A-2). The plumbing fixtures indicate a restaurant Occupancy Classification. Please revise that to an arena (A-3), and use that classification to determine the required plumbing fixtures. Water closets are 1/75 for males and 1/40 for females. Lavatories are 1/200 for males, and 1/150 for females. These numbers would require one water closet for males, but two water closets for females. Please revise the calculations and provide the required female water closets on the plan.
2. Sheet A1; Exiting Plan: The IBC Table 1017.2 indicates the maximum exit access travel distance for an A Occupancy Classification is 250' (with sprinkler). Please indicate on the plan the exit access travel distance from the most remote point to the accessible exit meets that requirement.
3. Sheet A2; Floor Plan: At the Brewery on the north end, a note indicates "New Brew House = 30 SF". Please indicate on the plan the referenced 30 SF.
4. Sheet A7; Partition Detail 6: A note indicates to see Sheet A6 for wall stud gauge. Please revise that reference to Sheet A7.
5. General: Please provide written responses to all review comments.
05/07/2020 ROBERT SHERRY WATER REVIEW Completed
05/07/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/07/2020 JPEELDA1 FIRE REVIEW Reqs Change Revise exiting plan to show travel distance and occupant loads. Egress to NW side door by kitchen is obstructed by electrical room.
05/12/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide sediment traps for the gas supply to the water heaters. Reference: Section 408.4, IFGC 2018.
2. If the gas piping branch serving the unit heaters and the water heaters has been sized using Table 402.4 (2), IFGC 2018, it is undersized. Revise the pipe sizes or consider using Table 402.4 (3), IFGC 2018.