Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM02876
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/07/2020 | SAMUEL ROGERS | ZONING | REVIEW | Approved | |
| 05/07/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The two Type I exhaust hoods require 1282 CFM of make-up air in addition to the make up air provided by EC-1. Provide a listing of the outside air that is currently being provided to the space that will provide the 1282 CFM of make up air. Reference: Section 508.1, IMC 2018. |
| 05/07/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/07/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
| 05/07/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1; Code Review: This building is considered an A-3 Occupancy Classification (arena) with an accessory use of restaurant/bar (A-2). The plumbing fixtures indicate a restaurant Occupancy Classification. Please revise that to an arena (A-3), and use that classification to determine the required plumbing fixtures. Water closets are 1/75 for males and 1/40 for females. Lavatories are 1/200 for males, and 1/150 for females. These numbers would require one water closet for males, but two water closets for females. Please revise the calculations and provide the required female water closets on the plan. 2. Sheet A1; Exiting Plan: The IBC Table 1017.2 indicates the maximum exit access travel distance for an A Occupancy Classification is 250' (with sprinkler). Please indicate on the plan the exit access travel distance from the most remote point to the accessible exit meets that requirement. 3. Sheet A2; Floor Plan: At the Brewery on the north end, a note indicates "New Brew House = 30 SF". Please indicate on the plan the referenced 30 SF. 4. Sheet A7; Partition Detail 6: A note indicates to see Sheet A6 for wall stud gauge. Please revise that reference to Sheet A7. 5. General: Please provide written responses to all review comments. |
| 05/07/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/07/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/07/2020 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Revise exiting plan to show travel distance and occupant loads. Egress to NW side door by kitchen is obstructed by electrical room. |
| 05/12/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide sediment traps for the gas supply to the water heaters. Reference: Section 408.4, IFGC 2018. 2. If the gas piping branch serving the unit heaters and the water heaters has been sized using Table 402.4 (2), IFGC 2018, it is undersized. Revise the pipe sizes or consider using Table 402.4 (3), IFGC 2018. |