Permit Number: T20CM02870
Parcel: 10408076F

Address:
4405 N ORACLE RD

Review Status: Completed

Review Details: OTHER

Permit Number - T20CM02870
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018.
3. Show that the proposed HVAC equipment meets the minimum performance requirements of Section C403.3.2, IECC 2018 (e.g. COMcheck Mechanical Compliance Certificate).
4. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3, IMC 2018.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/04/2020 ARUIZ1 OUT TO CUSTOMER Completed