Permit Number: T20CM02840
Parcel: 10511061R

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T20CM02840
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/09/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide specifications for the ejector pumps. Verify that the electrical system has separately fused outlets for the ejector pumps. Reference: Section 303.2, IPC 2018.
2. Provide a direct connection to the drainage system. Reference: Section712.3.5, IPC 2018.
3. Revise the drain waste & vent riser diagram to reflect the new forced main and ejector pumps. Reference: Section 107.2.1, IBC 2018.
09/11/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide Electrical plans showing designated branch circuits and panels, including load calculations for the new or modified mechanical equipment.
Ref; 2018 IBC sec 107.2.1, 2017 NEC.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/20/2021 JGARCIA1 APPROVAL SHELF Completed
01/20/2021 JGARCIA1 OUT TO CUSTOMER Completed
01/20/2021 JGARCIA1 REJECT SHELF Completed