Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/09/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
09/09/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide specifications for the ejector pumps. Verify that the electrical system has separately fused outlets for the ejector pumps. Reference: Section 303.2, IPC 2018. 2. Provide a direct connection to the drainage system. Reference: Section712.3.5, IPC 2018. 3. Revise the drain waste & vent riser diagram to reflect the new forced main and ejector pumps. Reference: Section 107.2.1, IBC 2018. |
09/11/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide Electrical plans showing designated branch circuits and panels, including load calculations for the new or modified mechanical equipment. Ref; 2018 IBC sec 107.2.1, 2017 NEC. |