Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM02840
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/06/2020 | ALEXANDRA HINES | ZONING | REVIEW | Approved | |
| 05/06/2020 | AHINES2 | ENGINEERING | REVIEW | Passed | |
| 05/06/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/06/2020 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 05/06/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 05/08/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide ventilation calculations for the suite. Show how all of the animal areas (e.g. kennels, grooming, and quarantine) are complying with Section 403.2.1 (3), IMC 2018, Table 403.3.1.1 (including footnote b), IMC 2018. 2. Provide specifications for the proposed exhaust fan, EF 1-485. 3. Provide specifications for the proposed rooftop AC, RTU 1-485. Show that is meets the equipment performance and control requirements of Sections C403.3.2, C403.4, and C403.5, IECC 2018 (e.g. COMcheck Mechanical Compliance Certificate) |
| 05/08/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the property owner will allow the use of ABS pipe for this activity. See boxed note on sheet P1, "Landlord Notes." |
| 05/08/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/11/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide full compliance with the 2018 IECC for the lighting. |