Permit Number: T20CM02840
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02840
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2020 ALEXANDRA HINES ZONING REVIEW Approved
05/06/2020 AHINES2 ENGINEERING REVIEW Passed
05/06/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/06/2020 MARTIN BROWN FIRE REVIEW Approved
05/06/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/08/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide ventilation calculations for the suite. Show how all of the animal areas (e.g. kennels, grooming, and quarantine) are complying with Section 403.2.1 (3), IMC 2018, Table 403.3.1.1 (including footnote b), IMC 2018.
2. Provide specifications for the proposed exhaust fan, EF 1-485.
3. Provide specifications for the proposed rooftop AC, RTU 1-485. Show that is meets the equipment performance and control requirements of Sections C403.3.2, C403.4, and C403.5, IECC 2018 (e.g. COMcheck Mechanical Compliance Certificate)
05/08/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify that the property owner will allow the use of ABS pipe for this activity. See boxed note on sheet P1, "Landlord Notes."
05/08/2020 ROBERT SHERRY WATER REVIEW Completed
05/11/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide full compliance with the 2018 IECC for the lighting.