Permit Number: T20CM02760
Parcel: 133180090

Address:
1033 N KOLB RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02760
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2020 MARTIN BROWN FIRE REVIEW Approved
05/05/2020 LOREN MAKUS ENGINEERING REVIEW Passed
05/12/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/12/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Verify that adequate ventilation will be provided for the poposed use of the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.
05/12/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Demo keynote #5 calls for the plumbing fixtures to be repaired or replaced. A replacement faucet for the lavatory shall be a metering faucet. The metering faucet shall dispense a maximum of 0.25 gallons per metering cycle. The faucet cycle must last for at least 10-seconds for accessibility. Reference: Section 412.11, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
05/12/2020 ROBERT SHERRY WATER REVIEW Completed
05/14/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/14/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change Denied per Vance so he could resubmit an entire new set of drawings.
05/27/2020 MALLORY RESS ZONING REVIEW Approved