Permit Number: T20CM02758
Parcel: 11516040B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02758
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1; Exit Requirements: Per the IBC Table 1006.3.3(2), stories with 49 occupants or less may have one exit as long as the common path of egress travel (75') is not exceeded. Please indicate this on Sheet A1.
2. Sheet A1; Site Plan: North of this project is a note that indicates "NEW 6' X 12' CONCRETE SLABWITH METAL ROOF ABOVE". Structural calculations, drawings, and specifications must be provided for this structure.
3. Sheet A3.0; Wall Types: Please indicate the gauge of the new metal studs at the interior walls.
4. Sheet A3.0; New Floor Plan: Please indicate the required high/low drinking fountain (or single point of use dispenser) and the service sink on the plan.
5. Sheet A3.0; Wall Types: On Wall Type 3 (above the ceiling), please indicate the bracing size, spacing, and connections (size and quantity) at the top of the wall and to the roof deck above.
6. Sheet A4.0; Reflected Ceiling Plan: Please indicate the exit signs on the plan.
7. Sheet A5.0; Break Room Elevations 3 and 4: Per the IBC Section 1109.3, sinks in accessible areas are required to be accessible. The height of the counter/sink in the Break Room is required to be a maximum of 2'-10" above finish floor.
8. General: Please provide written responses to all review comments.
05/11/2020 ARUIZ1 FIRE REVIEW Needs Review
05/11/2020 ARUIZ1 MECHANICAL-COMMERCIAL REVIEW Needs Review
05/11/2020 ARUIZ1 PLUMBING-COMMERCIAL REVIEW Needs Review
05/11/2020 ARUIZ1 WATER REVIEW Needs Review