Permit Number: T20CM02750
Parcel: 116094210

Address:
3159 W SALVIA DR

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM02750
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2020 JPEELDA1 FIRE REVIEW Reqs Change The fire flow requirement (the amount of water available from the hydrant) for a house this size is 1750 GPM @ 20 psi. Please contact Fred Coy (fred.coy@tucsonaz.gov) and ask him to model the fire flow for this address. If the fire flow can be obtained, include the correspondence from Fred as part of the construction documents, and the plans will be approved. If the hydrant cannot support this number, a residential sprinkler system will be required, and a note indicating sprinklers will be installed must be added to the cover sheet of your plans.
08/03/2020 STEVE SHIELDS ZONING REVIEW Approved
08/05/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Completed