Permit Number: T20CM02741
Parcel: 12402021A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02741
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
05/04/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide an air return for the office to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2018
05/04/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a service sink and drinking fountains per Table 2902.1, IBC 2018 and Section 410.3, IPC 2018.
05/04/2020 MARTIN BROWN FIRE REVIEW Approved
05/04/2020 ROBERT SHERRY WATER REVIEW Completed
05/05/2020 ELISA HAMBLIN ZONING REVIEW Approved
05/05/2020 EHAMBLI1 ENGINEERING REVIEW Passed
05/05/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G1.00; General Building Requirements: The Occupancy Classification is listed as Mercantile (M). The IBC Section 309 indicates Mercantile as the use of a building for the display and sale of merchandise. The IBC Section 304 indicates Business (B) as the use of a building for office, professional, or service-type transactions. It would appear the B Occupancy Classification would be a better fit than the M Occupancy Classification. Please verify.
2. Sheet G1.00; General Building Requirements: Please revise the requirements as needed for the B Occupancy Classification, including Occupant Load and Plumbing Fixture requirements.
3. Sheet A1.00; Breakroom Elevation D: Per the IBC Section 1109.3, sinks in accessible areas are required to be accessible. The height of the counter/sink in the Breakroom is required to be a maximum of 2'-10" above finish floor. Please verify.
4. Sheet A1.00; Grab Bars: Please indicate an elevation (in addition to Elevation C) the restroom grab bars per the ICC/ANSI Figures 604.5.1 and 604.5.2.
5. General: Please provide written responses to all review comments.
05/05/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed