Permit Number: T20CM02740
Parcel: 140580010

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM02740
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Indicate the AIC rating of the All-In-One service panel.
2. Indicate the sizes, types, number of riser conductors.
3. Indicate the address of the project on the electric plan.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.