Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T20CM02740
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Indicate the AIC rating of the All-In-One service panel. 2. Indicate the sizes, types, number of riser conductors. 3. Indicate the address of the project on the electric plan. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |