Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T20CM02740
Parcel: 140580010

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T20CM02740
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2020 LOREN MAKUS ENGINEERING REVIEW Passed
05/01/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide a complete line diagram include;
(a) Fault current rating of the service equipment and associated downstream equipment.
(b) Voltage, Amp, phase.
(c) All conductor, conduit sizes and types.
(d) Location of the Temp Electrical Service on the site plan.
(e) Detail showing the type of service equipment, configuration, mounting.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.
05/01/2020 MALLORY RESS ZONING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
05/04/2020 ARUIZ1 OUT TO CUSTOMER Completed