Permit Number: T20CM02738
Parcel: 12411021E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02738
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2020 MALLORY RESS ZONING REVIEW Approved
05/01/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide heating/cooling load calculations to justify the capacities of the new heat pumps. Reference: Section C403.1.1, IECC 2018.
05/01/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide compliance with the current 2018 IECC for the lighting.
05/01/2020 JOHN VAN WINKLE ENGINEERING REVIEW Passed
05/01/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A-001; Toilet Mounting Heights (Elevation F): Please provide the dimension from the back wall to the vertical grab bar per the ICC/ANSI Figure 604.5.1.
2. Sheet A-001; Occupancy Schedule; Non-Separated Uses: The Occupancy Schedule indicates 1845 GSF for the B Occupancy and 2044 SF for the Assembly/Storage Occupancy. The Non-Separated Uses indicates 1283 SF for the A Occupancy and 2607 SF for the B Occupancy. Please coordinate.
3. Sheet A-100; Code Analysis Floor Plan: Per the IBC Section 1017.3, the measurement of the exit access travel distance shall be along natural and unobstructed paths of horizontal and vertical travel. Please revise the plan.
4. Sheet A-210; Keyed Notes: Note 221 references Detail 5/A-901 for backing at the TV. Please revise that reference.
5. Sheet A-310; Reflected Ceiling Plan: Please indicate the new/existing exit signs on this plan.
6. General: Please provide written responses to all review comments.
05/01/2020 ROBERT SHERRY WATER REVIEW Completed
05/01/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide metering faucets for the lavatories in the public restrooms, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Revise the hot water distribution piping so that the distance from the hot water source to the hot water termination (i.e. the stop valve) for each public lavatory complies with the requirements of Section C404.5, IECC 2018.
05/01/2020 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
05/04/2020 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/11/2020 ARUIZ1 APPROVAL SHELF Completed
05/11/2020 ARUIZ1 OUT TO CUSTOMER Completed
05/11/2020 ARUIZ1 REJECT SHELF Completed