Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM02738
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/01/2020 | MALLORY RESS | ZONING | REVIEW | Approved | |
05/01/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide heating/cooling load calculations to justify the capacities of the new heat pumps. Reference: Section C403.1.1, IECC 2018. |
05/01/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide compliance with the current 2018 IECC for the lighting. |
05/01/2020 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
05/01/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A-001; Toilet Mounting Heights (Elevation F): Please provide the dimension from the back wall to the vertical grab bar per the ICC/ANSI Figure 604.5.1. 2. Sheet A-001; Occupancy Schedule; Non-Separated Uses: The Occupancy Schedule indicates 1845 GSF for the B Occupancy and 2044 SF for the Assembly/Storage Occupancy. The Non-Separated Uses indicates 1283 SF for the A Occupancy and 2607 SF for the B Occupancy. Please coordinate. 3. Sheet A-100; Code Analysis Floor Plan: Per the IBC Section 1017.3, the measurement of the exit access travel distance shall be along natural and unobstructed paths of horizontal and vertical travel. Please revise the plan. 4. Sheet A-210; Keyed Notes: Note 221 references Detail 5/A-901 for backing at the TV. Please revise that reference. 5. Sheet A-310; Reflected Ceiling Plan: Please indicate the new/existing exit signs on this plan. 6. General: Please provide written responses to all review comments. |
05/01/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
05/01/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide metering faucets for the lavatories in the public restrooms, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. Revise the hot water distribution piping so that the distance from the hot water source to the hot water termination (i.e. the stop valve) for each public lavatory complies with the requirements of Section C404.5, IECC 2018. |
05/01/2020 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
05/04/2020 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/11/2020 | ARUIZ1 | APPROVAL SHELF | Completed |
05/11/2020 | ARUIZ1 | OUT TO CUSTOMER | Completed |
05/11/2020 | ARUIZ1 | REJECT SHELF | Completed |