Permit Number: T20CM02707
Parcel: 14117680A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02707
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/03/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/03/2020 ROBERT SHERRY WATER REVIEW Completed
06/18/2020 LOREN MAKUS ENGINEERING REVIEW Approved
06/29/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/01/2020 STEVE SHIELDS ZONING REVIEW Approved
07/08/2020 JPEELDA1 FIRE REVIEW Approved IFC 2018 907.2.7 Group M. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group M occupancies where one of the following conditions exists:
The combined Group M occupant load of all floors is 500 or more persons
The Group M occupant load is more than 100 persons above or below the lowest level of exit discharge
Please provide note stating that fire alarms are required
07/09/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A101; Floor Plan: Near Grid Lines Z.2 and 7, a section cut references 1/AXXX. Please revise that reference.
2. Sheet A201; Reflected Ceiling Plan: Please indicate the exit lighting on this plan, or reference the Electrical Lighting Plan.
3. Sheet A402; Section 3: This section is cut on the plan at a location where the masonry column centerline is at Grid Line Z.2 rather than Z.1 as noted. Please verify.
4. Sheet A402 (Section 2); Sheet A501 (Section 1): Section 2/A402 indicates a steel frame. Please add that frame to the enlarged Wall Section 1/A501.
5. Sheet A601; Wall Types 1 and 2: Please indicate on these Wall Type Sections the top of the masonry wall, or reference the Wall Sections on Sheet A501.
6. Sheet S1.1; General Structural Notes (Foundations): A note indicates the foundation design is based on a soil report. Please provide that soil report for review.
7. Sheet S2.1; Boxed Note: This note indicates foundations are preliminary, not for construction. However, the Metal Building Calculations and Deferred Submittal Drawings are completed. The engineer of record should follow the IBC Section 107.3.4.1 and review those drawings and calculations, indicating that those documents have been reviewed and found to be in general conformance with the construction documents.
8. General: Please provide the structural calculations for the foundation design.
9. General: Please provide a Special Inspection Certificate with Parts A and B completed.
10. General: Please provide written responses to all review comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/13/2020 JGARCIA1 APPROVAL SHELF Passed
07/13/2020 JGARCIA1 OUT TO CUSTOMER Completed
07/13/2020 JGARCIA1 REJECT SHELF Completed