Permit Number: T20CM02686
Parcel: 136030200

Address:
8543 E 24TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM02686
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2020 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Submit a construction Plan Set following the guidelines at: https://www.tucsonaz.gov/pdsd/residential-permits

PROVIDE A SITE PLAN AND WALL SECTION.

A WALL SECTION MUST SHOW FOUNDATION WITH 1/2" X 10" ANCHOR BOLTS, TREATED SILL PLATES 2" ABOVE EXTERIOR CONCRETE WALKWAYS OR 6" ABOVE EARTH.

ALSO SHOW TYPE OF SHEATHING AND TYPE & AMOUNT OF INSULATION FOR 2018 irc CODE COMPLIANCE.
06/26/2020 ELISA HAMBLIN ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Elisa Hamblin, AICP; Principal Planner
Zoning Review

PROJECT: T20CM02686
8543 E 24th St
Enclose Carport to Living Space
Residential (2nd Review)

TRANSMITTAL DATE: June 26, 2020

The room addition plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

1. Per previous comments from May 15, 2020, provide a plot plan that meets the requirement below.

Residential plot plan requirements can be found at https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf

If you have any questions about this transmittal, please contact me at Elisa.Hamblin@tucsonaz.gov or (520) 837-4966