Permit Number: T20CM02685
Parcel: 11615088L

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20CM02685
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 1; Sheet G2.1; Code Plan: Please measure the exit access travel distance per the IBC Section 1017.3. The travel distance measurement must be along the natural and unobstructed path of horizontal and vertical egress travel (not diagonal). Please revise.
2. Previous Comment 3; Sheet A7.1: Please locate the side wall horizontal grab bar per the ICC/ANSI Figure 604.5.1.
3. Previous Comment 3; Sheet A7.1 (Elevation 23): Please locate the back wall horizontal grab bar per the ICC/ANSI Figure 604.5.2.
4. General: Please include all drawings in the new submittal.
5. General: Please provide written responses to all review comments.