Permit Number: T20CM02685
Parcel: 11615088L

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T20CM02685
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/04/2020 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G2.1; Code Plan: Please measure the exit access travel distance on the plan per the IBC Section 1017.3.
2. Sheet G2.1; Project Data: Many of the code section references are from the 2012 IBC. Please review and revise all references to the 2018 IBC.
3. Sheet A7.1: Please provide dimensioned elevations for the grab bars in a typical restroom per the ICC/ANSI Figures 604.5.1 and 604.5.2.
4. General: Please provide written responses to all review comments.
06/04/2020 ROBERT SHERRY WATER REVIEW Completed
06/04/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/04/2020 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/05/2020 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
06/08/2020 JPEELDA1 FIRE REVIEW Approved