Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T20CM02685
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2020 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G2.1; Code Plan: Please measure the exit access travel distance on the plan per the IBC Section 1017.3. 2. Sheet G2.1; Project Data: Many of the code section references are from the 2012 IBC. Please review and revise all references to the 2018 IBC. 3. Sheet A7.1: Please provide dimensioned elevations for the grab bars in a typical restroom per the ICC/ANSI Figures 604.5.1 and 604.5.2. 4. General: Please provide written responses to all review comments. |
| 06/04/2020 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 06/04/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 06/04/2020 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 06/05/2020 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 06/08/2020 | JPEELDA1 | FIRE | REVIEW | Approved |